Voltage drop formula
Every wire has resistance, so part of the supply voltage is lost along the run. For single-phase and DC circuits the standard approximation is:
VD = 2 × K × I × L ÷ CM
For three-phase circuits replace the 2 with √3 (1.732). Here K is the resistivity of the conductor in ohm-circular-mils per foot (12.9 for copper and 21.2 for aluminum at 75 °C), I is the load current in amps, L is the one-way length in feet and CM is the conductor's cross-section in circular mils from NEC Chapter 9, Table 8. The percentage drop is VD ÷ supply voltage × 100.
Example: 20 A at 100 feet
A 120 V single-phase circuit carries 20 A to a load 100 ft away using 12 AWG copper (6,530 circular mils):
- VD = 2 × 12.9 × 20 × 100 ÷ 6,530 = 7.90 V.
- Percentage: 7.90 ÷ 120 = 6.6% — well above the commonly recommended 3% for a branch circuit.
- Upsizing to 10 AWG (10,380 cmil) gives 4.97 V (4.1%), and 8 AWG (16,510 cmil) gives 3.13 V (2.6%), which meets the 3% target.
This is why long runs to garages, sheds and well pumps often need wire one or two sizes larger than the breaker alone would require.
Ampacity: the second check
Voltage drop is about performance; ampacity is about safety. The wire must also be able to carry the current without overheating. The calculator checks each gauge against NEC Table 310.16 (no more than three current-carrying conductors, 30 °C ambient) for the 60 °C, 75 °C and 90 °C insulation columns, and applies the small-conductor limits of NEC 240.4(D): 14 AWG copper on 15 A, 12 AWG on 20 A and 10 AWG on 30 A overcurrent protection. The recommended size is the larger of the two requirements. Metric mm² equivalents are shown for reference.
Safety and code notes
Results are estimates for planning. Real installations must also consider conductor temperature ratings of terminals, ambient temperature and bundling corrections, conduit fill, continuous loads (sized at 125%), motor starting current and local amendments to the electrical code. Outside North America, wiring follows IEC 60364 or national standards such as GB 50054 in China, which use mm² sizes and different tables. Always have electrical work designed and inspected by a licensed electrician.
Frequently asked questions
What is an acceptable voltage drop?
The NEC informational notes recommend no more than 3% on a branch circuit and 5% total for feeder plus branch circuit.
Is the distance one-way or round trip?
Enter the one-way distance from the panel to the load. The formula's factor of 2 accounts for the return conductor.
Why does aluminum wire need a larger size?
Aluminum has about 61% of copper's conductivity, so it needs roughly two AWG sizes larger to carry the same current with the same drop.
What gauge wire do I need for a 20 amp circuit?
12 AWG copper is the minimum for a 20 A breaker under NEC 240.4(D); longer runs may need 10 AWG or larger to keep voltage drop under 3%.